Herguth Laboratories
Client Log In Online Registration Product Order
 

Transformer Oil

Herguth Laboratories, Inc. provides in depth analysis of transformer oils, using state-of-the-art laboratory instruments and certified technicians. The tests listed are designed to assist you in maintaining your transformer oil.

Quality Programs
ISO 9002

Nuclear Grade - 10 CFR 50 Appendix “B”

If you do not find the tests you need listed, please call 800-645-5227. We can design custom test packages for you upon request.

Dissolved Gas Analysis
ASTM D-3612 (Reported in ppm

Oil Temp - C
Hydrogen - H2
Methane - CH4
Ethane - C2H6
Ethylene - C2H4
Acetylene - C2H2
Carbon Monoxide- CO
Carbon Dioxide - CO2
Nitrogen - N2
Oxygen - O2

Oil Screening Analyses
Acid Number ASTM D-974
Appearance HL-1121
Color ASTM ASTM D-1500
Specific Gravity ASTM D-1298
Dielectric Strength ASTM D-877
Interfacial Tension ASTM D-971
Power Factor @ 25C ASTM D-924
Power Factor @ 100C ASTM D-924
Water by Karl Fischer ASTM D-1533

General Transformer Oil Testing
Acid Number ASTM D-974
Appearance ASTM D-1121
Color ASTM ASTM D-1500
Copper Corrosion by Copper Strip SEE ASTM 1275 ASTM D-130
Density by Digital Density Meter ASTM D-4052
Density, Relative Density (Specific Gravity ASTM D-1298
Dielectric Breakdown of Insulating Oils ASTM D-1816
Dielectric Strength of Insulating Oils ASTM D-877
Dissolved Gas Analysis (DGA) ASTM D-3612
Filter Patch Test HL-1142
Flash & Fire Point by Cleveland Open Cup ASTM D-92
Flash or Fire Point by Cleveland Open Cup ASTM D-92
Furanic Compounds (Cellulose Degradation) ASTM D-5837
HIAC Particle Count HL-1184
HMB Biomass Culture Study HL-1161
Interfacial Tension ASTM D-971
Metals by ICP (24 Elements) HL-1158
Metals by ICP Additional Elements (each) HL-1158
Microbial Growth HL-1126
Oxidation Inhibitor (DBPC / DBP) ASTM D-2668
Oxidation Stability (pressure vessel) ASTM D-2112
PCB Screen (A), PCB Level (B) HL-1147
Pour Point ASTM D-97
Power Factor @ 100C ASTM D-924
Power Factor @ 25C ASTM D-924
Power Factor @ 25c and 100C ASTM D-924
Refractive Index ASTM D-1218
Resistivity ASTM D-1169
Viscosity at 100F -SUS ASTM D-445
Viscosity, Kinematic 40C cSt ASTM D-445
Viscosity, Special Temperature ASTM D-445
Water by Karl Fischer ASTM D-1533

Sample Syringes
Sample syringes are available in 20, 30, 50 and 100 ml sizes with 3 way vales and plugs.

Sampling Transformer Oils
Detailed sampling instructions can be found in the American Society of Testing and Materials (ASTM) Standard Book Volume 10.03. These standard practices are and available through Herguth Laboratories, Inc. or www.astm.org

Standard Practices Specific to Sampling are:
D-923 Sampling Electrical Insulating Fluids
D-2759 Sample Gas from Transformer Under Positive Pressure
D-3305 Sampling Small Gas Volume in a Transformer
D-3316 Sampling Insulating Liquids for Gas Analysis and Determination of Water Content.

For more information call 1-888-HERGUTH (437-4884)